Exprement
Maximum Power Transfer Theorem
F Unit Objective
At the completion of this unit, you will be able to verify maximum
power transfer theorem.
F Procedure
Maximum power transfer theorem
states that in a linear, bilateral network, maximum power transfer takes place
to the load only when load impedance matches or equals with the equivalent
internal impedance (Thevenin’s impedance, RTH) of the network.
A) Maximum Power Transfer
Theorem for DC input voltage:
|
Step-1: Make connections as per above
wiring sequence given & check the complete wiring as per the circuit
arrangement.
Step-2: First keep the variable POT (P1)
at fully CCW position & switch ON the power supply and adjust voltage to +12V.
Step-3: Now take the readings of
Voltmeter & Ammeter at this POT position (i.e. at 0 ohm) & fill the
corresponding table.
Step-4: Switch OFF the supply and remove from the network
& also remove the network connection from load (RL) i.e. remove connections
of power supply, AM(-) - 70.
Now connect ohmmeter (Lab DMM) at 71 & 73 and set load (RL) to next
reading by slightly varying the POT; set RL=
500W.
Step-5: Now remove the ohmmeter & make connection again
as per wiring sequence and measure voltmeter & ammeter readings.
Step-6: Again remove supply & connect ohmmeter and set
POT value as per table and follow above procedure to measure corresponding
readings. Follow same procedure for each RL value.
Table
P2.9.1 DC input based Observation Table
RL (Ohms) |
Measured Current
(I) (in
mA) |
Measured Voltage
(V) (in
volts) |
O/P
power (in
mW) |
||
P=I2RL |
P=V2/
RL |
||||
0 W |
|
|
|
|
|
500 W |
|
|
|
|
|
1K |
|
|
|
|
|
1.5K |
|
|
|
|
|
2K |
|
|
|
|
|
3K |
|
|
|
|
|
4K |
|
|
|
|
|
6K |
|
|
|
|
|
8K |
|
|
|
|
|
10K |
|
|
|
|
|
NOTE: Each time set ‘RL’ (i.e. Load resistance) using
ohmmeter as per table by disconnecting RL from the network,
otherwise loading occurs.
The internal impedance (Thevenin’s
impedance, RTH) of the above network is equal to 1.5K, calculate RTH by shorting 51
& 62 and connect ohmmeter at 55 & 63.
i.e. RTH = (Ra // Rc )
+ (Rb) = (1K // 1K) + (1K) = 1.5K.
B) Maximum Power
Transfer Theorem for AC input voltage:
Fig. P2.9.2 AC input voltage maximum Power
Transfer Theorem
Step-1: Make connections as per above
wiring sequence given & check the complete wiring as per the circuit
arrangement.
Step-2: Follow the same procedure as of
DC measurement & fill the below corresponding table as per POT (load)
value.
Table
P2.9.2 AC input based Observation Table
RL (Ohms) |
Measured
Voltage (V) (in
Vpp) |
O/P
power (in mW) P=V2/ RL |
0 |
|
|
500 |
|
|
1K |
|
|
1.5K |
|
|
2K |
|
|
3K |
|
|
4K |
|
|
6K |
|
|
8K |
|
|
10K |
|
|
NOTE: 1) Each time set ‘RL’ (i.e. Load
resistance) using ohmmeter as per table by disconnecting RL from the
network, otherwise loading occurs.
2) In AC measurement using CRO/DSO, observe the peak-to-peak value
& fill the corresponding table.
F Conclusion
As the theorem stated for the maximum
transferred power to the load, when load impedance matches with the network
internal impedance (Thevenin’s impedance, RTH). Hence from the observed
readings; at 1.5K load impedance you got maximum power, because internal
network impedance is of 1.5K. Hence maximum power transfer theorem is verified.
This is followed to be true for DC 12V as well as AC 12VRMS voltages.
F Equipments
required
1.
DC power Supply 0 – 15V (set to
12V).
2.
DMM.
3.
CRO/DSO.
4.
CT Master Unit (for 12VRMS
AC supply).
5.
Panel No. P2.
©other source
1 Comments
not good
ReplyDeleteThank you